TABLE 1 – HV CABLE CURRENT CARRYING CAPACITIES 

Nominal conductor Cross-section (sq.mm)

Allowable Current when installed underground (A) (Armoured)

Allowable Current when installed underground (A) (Armoured)

Allowable Current when installed      in air (A) (Armoured)

Allowable Current when installed      in air (A) (Armoured)

Remarks

1 core

3 cores

1 core

3 cores

50

-

181

-

205

 

70

-

220

-

253

 

95

-

263

-

307

 

120

 

298

 

352

 

150

-

332

-

397

 

185

-

374

-

453

 

240

-

431

-

529

 

150

361

 

473

 

 

185

406

 

543

 

 

240

469

 

641

 

 

300

526

 

735

 

 

400

590

 

845

 

 

500

679

-

990

-

 

630

774

-

1140

-

-

Note:   (1)    Reference soil temperature in ground           20

(2)    Reference ambient temperature in air            30

(3)    Reference thermal soil resistivity                   1.5K.m/W

(4)    Depth of laying                                            0.8 m

(5)  Reference installation :       Table B.2 for single-core cables and B.6 for three core

                                                cables of IEC 60502-2

 

 

TABLE 2 – LV CABLE CURRENT CARRYING CAPACITIES 

Nominal Conductor Cross-section (sq.mm)

Allowable Current when

installed underground (A)

(Armoured)

Allowable Current when

installed in air  (A)

 (Armoured)

2 cores

3 cores

2 cores

3 cores

4

46

39

49

42

6

58

49

63

54

10

77

65

86

75

16

100

84

115

100

25

129

107

149

127

35

155

129

185

158

50

183

153

225

192

70

225

188

289

246

95

270

226

352

298

120

306

257

410

346

150

343

287

473

399

185

387

324

542

456

240

448

375

641

538

Note:   (1)    Reference soil temperature in ground           20

(2)    Reference ambient temperature in air           30

(3)    Reference thermal soil resistivity                   2.5K.m/W

(4)    Depth of laying                                            0.7 m

(5)  Reference installation :       Table B.52.3 , B.52.5 for underground and B.52.12

                                                For in air of IEC 60364-5-52

 

  

TABLE 3 – 33KV CABLE RESISTANCE AND REACTANCE

Nominal conductor cross-section (sq.mm)

1 CORE

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

185

0.1272

0.1137

240

0.0973

0.1097

300

0.0781

0.1074

400

0.0618

0.1048

500

0.0492

0.1015

630

0.0394

0.0989

 

TABLE 4 – 11KV CABLE RESISTANCE AND REACTANCE

Nominal conductor cross-section (sq.mm)

1 CORE

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

150

0.159

0.1077

185

0.1273

0.1057

240

0.0975

0.1021

300

0.0783

0.1015

400

0.0621

0.1051

500

0.0496

0.0990

630

0.0398

0.0934

 

 

TABLE 5 – 11KV CABLE RESISTANCE AND REACTANCE  

Nominal conductor cross-section (sq.mm)

3 CORE

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

50

0.494

0.0876

70

0.343

0.0848

95

0.247

0.0820

120

0.196

0.0804

150

0.160

0.0786

185

0.1278

0.0773

240

0.0981

0.0754

 

TABLE 6 – 3.3KV CABLE RESISTANCE AND REACTANCE

Nominal conductor cross-section (sq.mm)

1 CORE

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

150

0.159

0.1065

185

0.1274

0.1042

240

0.0975

0.1011

300

0.0783

0.1007

400

0.0622

0.0982

500

0.0496

0.0959

630

0.0399

0.0933

 

TABLE 7 – 3.3KV CABLE RESISTANCE AND REACTANCE

Nominal conductor cross-section (sq.mm)

3 CORE

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

50

0.494

0.0842

70

0.343

0.0816

95

0.247

0.0790

120

0.196

0.0776

150

0.160

0.0760

185

0.1279

0.0748

240

0.0983

0.0734

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 8 – LV CABLE RESISTANCE AND REACTANCE  

Nominal conductor cross-section (sq.mm)

Resistance (Ohm/km)

Reactance (Ohm/km)

AC 90 °C

 

4

5.88

0.092

6

3.93

0.088

10

2.33

0.083

16

1.47

0.081

25

0.927

0.079

35

0.669

0.077

50

0.494

0.076

70

0.342

0.075

95

0.247

0.073

120

0.196

0.072

150

0.160

0.073

185

0.1283

0.073

240

0.0987

0.072

 

 

 

'자료실 > 전기 자료' 카테고리의 다른 글

DNV RP-B401  (0) 2012.10.08
NACE Code  (0) 2012.10.08
전기방식이란  (0) 2012.10.08
Harmonic은 왜 생기나?  (0) 2012.08.22
[스크랩] 분리형광전식 감기기  (0) 2012.03.31